1- Above the exit door
There must be a guidance marking above the main exit door.
There must be guidance markings above the other doors on the way out.
| |
 |
|
2- Outside of the last exit door
There must be lighting device outside the last exit door for the people not to be in dark at outside and not to slow down the evacuation. |
|
|
|
|
|
|
|
|
|
 |
|
3- Lighting at the corridors and at the end of the corridors guidance markings
The corridors must be illuminated in termes evacuation. There must be guidance markings above the door at the end of the corridor. |
|
 |
|
4- Turning Points
There must be lighting device and guidance markings for not to slow down the evacuation speed if there is a need to change direction during evacuation. |
|
|
|
|
|
|
|
|
|
 |
|
5- Intersection Points of the corridors
There must be a lighting device at the intersection points of the corridors in terms of persons coming from different directions and without a collision to continue their ways without a problem and when the persons reached the intersection points guidance marking shall be seen at this point. |
|
 |
|
6- Next to each non-illuminated guidance marking
The non-illuminated guidance markings lightened form outside must be lightened with an emergency lighting devices with battery.
The lighting device distance to the marking must be maximum 2 meters in horizontal plane.
|
|
|
|
|
|
|
|
|
|
|
 |
|
7- Floor Level Changed Places
There must be lighting device at the places where the floor level changes for the people not to tumble during the evacuation.
For the people who tumble at this places they can be an obstacle for those behind him as well as he has a risk of smash and injury. |
|
 |
|
8- At the stairs
As in the previous article there must be an emergency lighting device at the stairs.
The emergency lighting device must be located to a place nearest to lower side of the stairs by the way of not to create the shadow of the stairs. Fire staris should be assessed and clarified in this context. |
|
|
|
|
|
|
|
|
|
 |
|
9- In escalators
The escalators turn into normal stairs in electric cuts. As in the previous article there must be an emergency lighting device in these kinds of places. The emergency lighting device must be located to a place nearest to lower side of the stairs by the way of not to create the shadow of the stairs. |
|
 |
|
10-At the places where the fire extinguisher device located
In case of fire the fire extinguisher tubes and fire cabinet must be visible with regard to the fire emergency response.
At this point of view there must be an emergency lighting device at these kinds of points and must be located to fire extinguisher device maximum 2 meters away in horizontal plane. |
|
|
|
|
|
|
|
|
|
|
 |
|
11- At the places where the fire alarm button located
The building may be evacuated immediately for a sudden reason; the fire alarm buttons must be visible with regard to start the evacuation by activating alarm system. At this point of view there must be an emergency lighting device at these kinds of points and must be located to fire alarm buttons maximum 2 meters away in horizontal plane. |
|
 |
|
12- At the places where the first-aid materials located
The first – aid materials must be visible with regard to be addressed immediately by applying first aid to the injured people at emergency situations. At this point of view there must be an emergency lighting device at these kinds of points and must be located to first-aid equipment maximum 2 meters away in horizontal plane. |
|
|
|
|
|
|
|
|
|
|
 |
|
13- In First – aid Rooms
The First-aid rooms must be visible in terms of emergency response by applying first aid to the injured people at emergency situations. Also there must be emergency lighting inside the room. |
|
 |
|
14- At the places where the building layout scheme located
The points where the building layout and evacuation plans located must be visible. At this point of view there must be an emergency lighting device located maximum 2 meters away in horizontal plane. |
|
|
|
|
|
|
|
|
|
|
 |
|
15- In elevators
There must be an emergency lighting device in elevators according to the EN81-1 standards. |
|
 |
|
16- In Handicapped Toilets and the toilets larger than 8 m²
Finding the door in dark environment is hard in these kinds of places and it can cause panic, falling down and injuries in darkness. There must be an emergency lighting device inside the toilet for getting out of the people without an injury from these kinds of places. | |
|
|
|
|
|
|
|
|
|
|
|
17- At the places where the moving machines with high risks of hazars or the chemical baths are located
There must be an emergency lighting device for avoiding the accidents at high danger risk locations.
Also the emergency lighting must be made to these kinds of places.
| |
|
|
18- In Generator Rooms
There must be an emergency lighting device with regard to control and operate the electric system, if necessary, at electric production locations.
Also the emergency lighting must be made to these kinds of places.
| |
|
|
|
|
|
|
|
|
|
|
|
19- Electric and Command Rooms
There must be an emergency lighting device with regard to control and operate the electric system If necessary at electric distribution locations.
Also the emergency lighting must be made to these kinds of places.
|
|
|
|
20- In Garages and Pedestrian Paths
There must be an emergency lighting device for an evacuation with no risk in indoor garages and pedestrian paths inside the building.. | |